Smoke alarms in new homes: what the National Construction Code requires
The NCC 9.5 rules for new builds, why interconnection was added in 2014, and the current AS 3786 edition.
General information, not legal or electrical advice. Check the current rules with your state authority and use a licensed electrician for any hardwired work.
Short answer
Every new house in Australia must have smoke alarms that meet AS 3786, run on mains power where the building has it, and are interconnected where there is more than one. They go in every hallway serving bedrooms and on every storey, on the ceiling at least 300mm from the wall. That is the National Construction Code, and the interconnection rule has been in it since NCC 2014.
If you are building, extending or doing a major renovation, the state retrofit rules on the other pages matter less than the National Construction Code (NCC). The NCC sets the minimum for new work everywhere in Australia, and your building surveyor or certifier checks it. This page explains the smoke alarm part in plain English.
What does the NCC require for smoke alarms in new homes?
Housing Provisions clause 9.5.1 says smoke alarms must [NCC 2025 Part 9.5]:
- be located as set out in clauses 9.5.2 and 9.5.4
- comply with AS 3786
- "be powered from the consumer mains source where a consumer mains source is supplied to the building"
- "be interconnected where there is more than one alarm".
The interconnection rule applies within a single dwelling. The code's explanatory note says alarms in one house "need not be interconnected with alarms in another dwelling or a private garage which does not belong to the Class 1a dwelling" [NCC 2025 Part 9.5]. NSW has its own version of 9.5.1 with substantially the same wording [NCC 2025 NSW 9.5].
Where must smoke alarms go in a new house?
Clause 9.5.2 sets the locations for a house (Class 1a) [NCC 2025 Part 9.5]:
- on any storey with bedrooms, in every corridor or hallway associated with a bedroom, or if there is no corridor, between the bedrooms and the rest of the building
- on each other storey that has no bedrooms.
That is the minimum. It does not require an alarm inside each bedroom. Queensland adds that for its homes through its own law, and most fire services recommend it everywhere. See where to install smoke alarms.
How far from walls and ceiling apexes?
Clause 9.5.4 says alarms go on or near the ceiling [NCC 2025 Part 9.5]:
- On the ceiling, at least 300mm from the corner where the wall meets the ceiling.
- On a sloping ceiling, between 500mm and 1,500mm from the high point or apex.
- If the ceiling isn't possible, on the wall, between 300mm and 500mm below the ceiling.
The reason is "dead air space". The code explains it as "an area in which trapped hot air will prevent smoke from reaching the alarm. This space generally occurs at the apex of cathedral ceilings, the corner junction of walls and ceilings and between exposed joists" [NCC 2025 Part 9.5].
What about a garage under the house?
Where a home sits over a garage that doesn't belong to it (a "garage top dwelling"), the code requires a heat alarm in the garage, interconnected to the dwelling's smoke alarms [NCC 2025 Part 9.5]. A garage that belongs to the home can have a different type of alarm suited to the space, as long as AS 3786 smoke alarms are installed elsewhere in the house [NCC 2025 Part 9.5].
When did interconnection become compulsory for new homes?
In the 2014 edition of the code. The NCC 2013 explanatory note said: "There is no requirement in the BCA that smoke alarms be interconnected" [NCC 2013 Vol 2]. NCC 2014 changed clause 3.7.2.2 to require alarms to "be interconnected where there is more than one alarm", and its explanatory note gave the reason: interconnection "will increase the likelihood of sleeping occupants becoming aware of the detection of smoke" [NCC 2014 Vol 2].
Most states give 1 May 2014 as the start date, for example the NT Government and Tasmania Fire Service [nt.gov.au] [TFS]. Western Australia is different: its regulations exempt homes whose building permit was applied for before 1 May 2015 [WA Building and Energy].
Why did the code change? The sound through a closed door
The Australian Building Codes Board's 2013 impact statement on interconnection set out the problem in numbers. About 75 dBA at 3,100 Hz is typically considered the sound level needed to wake sleeping people, and AS 3786 alarms produce 85 dBA at 3,100 Hz. In one study cited in the statement, with doors closed, the level at the bedhead in other rooms averaged 36 dBA [ABCB RIS 2013]. In other words, an alarm in the hallway may be nowhere near loud enough to wake someone behind a closed bedroom door. Interconnected alarms in the bedrooms fix that.
Which edition of the NCC applies?
NCC 2025 was published on 1 May 2026, and the states are adopting it on different dates [NCC 2025 adoption]. For smoke alarms it makes no practical difference, because the smoke alarm clauses read the same in NCC 2022 and NCC 2025 [NCC 2022 Part 9.5] [NCC 2025 Part 9.5].
| State or territory | NCC 2025 adopted |
|---|---|
| ACT | 1 May 2026 (12 month transition) |
| Victoria | 1 May 2026 |
| WA | 1 May 2026 (12 month transition) |
| NSW | 1 May 2027 |
| Queensland | 1 May 2027 |
| SA | 1 May 2027 |
| Tasmania | 1 May 2027 |
| NT | Not adopted (stays on NCC 2022) |
Sources: ABCB adoption table [NCC 2025 adoption] and the NT Government [NT NCC status].
What is AS 3786, and which edition is current?
AS 3786 is the Australian Standard for household smoke alarms. Its full title is "Smoke alarms using scattered light, transmitted light or ionization", which covers both photoelectric (scattered light) and ionisation alarms. The current edition is AS 3786:2023, published on 17 February 2023, which replaced AS 3786:2014 [AS 3786:2023]. The standard itself is a paid document, so I don't quote it.
Queensland's regulation names the 2014 edition specifically: alarms must "comply with AS 3786-2014" [Building Fire Safety Regulation 2008 (Qld)]. If you are buying alarms for a Queensland home and the box shows the 2023 edition, check with the maker or the Queensland Fire Department that it meets the Queensland rule.
Does the NCC require photoelectric alarms?
No. The NCC requires AS 3786, which covers both types. Back in 2014, the code's explanatory note on avoiding nuisance alarms said alarms should not go near cooking appliances and bathrooms, but if they must, "an ionisation type alarm is more suitable near bathrooms, while a photoelectric alarm may be used near cooking appliances" [NCC 2014 Vol 2]. The photoelectric requirement in Queensland and the NT comes from those jurisdictions' own laws [Building Fire Safety Regulation 2008 (Qld)] [NT Fire and Emergency Regs].
Do the NCC rules apply to my existing home?
Generally only when you build, extend or substantially renovate, and when your state's law points back to the code. WA, for example, requires alarms to meet the code that applied when they were installed [WA Building and Energy]. For what applies to an existing home, start with your state's page.
Sources
Every source below was read on the official page. Last checked: November 2026.
- Australian Building Codes Board: NCC 2025 Housing Provisions Part 9.5 Smoke alarms and evacuation lighting
- Australian Building Codes Board: NCC 2022 Housing Provisions Part 9.5 Smoke alarms and evacuation lighting
- Australian Building Codes Board: NCC 2025 Housing Provisions, Schedule 5 New South Wales, NSW Part 9.5 Smoke alarms
- Australian Building Codes Board: NCC 2013 BCA Volume Two (archived PDF)
- Australian Building Codes Board: NCC 2014 BCA Volume Two (archived PDF)
- Australian Building Codes Board: Regulation Impact Statement: Interconnection of Smoke Alarms (October 2013, PDF)
- Australian Building Codes Board: NCC 2025 state and territory adoption information
- Northern Territory Government (nt.gov.au): National Construction Code (NT adoption)
- Standards Australia: AS 3786:2023 Smoke alarms using scattered light, transmitted light or ionization (store page)
- Queensland Legislation: Building Fire Safety Regulation 2008, Part 5A, ss 55C to 55E (PDF)
- Northern Territory Government (nt.gov.au): Smoke alarms
- Tasmania Fire Service: Smoke alarms (home fire safety)
- Building and Energy, Government of Western Australia: Smoke alarm laws for homes being sold, rented and hired
- NT Legislation: Fire and Emergency Regulations 1996 (NT), Part 2A (reprint as in force at 16 July 2024, PDF)