General information, not legal or electrical advice. Check the current rules with your state authority and use a licensed electrician for any hardwired work.

Short answer

From 1 January 2027 every home in Queensland must have photoelectric smoke alarms that meet AS 3786-2014, contain no ionisation sensor, are hardwired or run on a non-removable 10-year battery, and are interconnected so they all sound together. You need one in every bedroom, in the hallway outside bedrooms, and on every storey. Homes being sold or leased have had to comply since 1 January 2022.

Queensland has the strictest home smoke alarm law in Australia. It is the only state that requires photoelectric, interconnected alarms in every bedroom of every existing home, not just new builds. This page covers the full rules from the Fire Services Act 1990 and the Building Fire Safety Regulation 2008, in plain English. If you only want to know what to do before the deadline, read the 1 January 2027 deadline guide.

What are the smoke alarm requirements in Queensland?

The Queensland Government's smoke alarm page says that to comply, smoke alarms must [qld.gov.au]:

  • be photoelectric
  • be interconnected with every other smoke alarm in the dwelling, so all activate and go off together
  • comply with Australian Standard AS 3786:2014, which is marked on the body of the alarm
  • not contain an ionisation sensor.

The legislation adds three more conditions [Fire Services Act 1990 (Qld)] [Building Fire Safety Regulation 2008 (Qld)]:

  • Power. Each alarm must be hardwired to the home's electricity supply, or powered by a battery that is built in so it can't be removed and made to last at least 10 years without recharging.
  • Age. Each alarm must have been manufactured less than 10 years before it is installed.
  • Working. Each alarm must operate when tested.

The Act defines "interconnected" by what the alarms do: each alarm sounds if the other detects smoke, and the other way around [Fire Services Act 1990 (Qld)]. It does not say how they connect, which is why both wired and wireless interconnection are used. The Queensland Fire Department says wireless alarms "connect without wiring, and can be installed yourself" [QFD fact sheet].

Which homes do the Queensland rules cover, and from when?

The law was phased in over ten years [qld.gov.au selling] [Fire Services Act 1990 (Qld)]:

Queensland smoke alarm law phases
FromApplies to
1 January 2017New homes, and homes substantially renovated, under a building application made on or after this date
1 January 2022Homes sold (contract to transfer the land) or leased (new tenancy or renewal)
1 January 2027All homes, including owner-occupied

"Homes" means houses, townhouses, units and manufactured homes. In the Act's words, a domestic dwelling is a Class 1a building or a sole-occupancy unit in a Class 2 building [Fire Services Act 1990 (Qld)]. A renovation is "substantial" if it, plus any structural work approved or done in the previous 3 years, is more than half the volume of the building [Fire Services Act 1990 (Qld)].

Registered caravans and motorhomes must also have a photoelectric smoke alarm [qld.gov.au]. The RTA says those first registered or transferred since 1 July 2024 must already comply, and all others from 1 January 2027 [RTA].

Where must smoke alarms be installed in Queensland?

Section 55C of the regulation sets the locations [Building Fire Safety Regulation 2008 (Qld)]:

  1. In each bedroom.
  2. On each storey with bedrooms: in the hallway if bedrooms open onto one, or otherwise in the part of the storey between the bedroom and the rest of the home.
  3. On each storey with no bedrooms: on the most likely path of travel to an exit.

The QFD checklist puts it simply: every bedroom, hallways or areas connecting bedrooms to the rest of the home, and every storey [QFD checklist]. For a typical single-storey three-bedroom house with one hallway, that means at least four alarms. A two-storey four-bedroom house with bedrooms upstairs needs at least four in the bedrooms, one in the upstairs hallway and one on the ground floor exit path. See where to install smoke alarms for worked layouts.

How far from lights, walls and air conditioners?

Unusually, Queensland writes exact distances into the regulation [Building Fire Safety Regulation 2008 (Qld)]. An alarm goes on the ceiling where practicable. It must not be within 300mm of a light fitting, within 300mm of the corner of a ceiling and wall, within 400mm of an air conditioner or forced-air vent, or within 400mm of ceiling fan blades. If it has to go on a wall, it must be 100mm to 300mm below the ceiling and more than 300mm from a corner. On a sloped ceiling it goes 500mm to 1,500mm from the apex.

Queensland smoke alarm placement distancesA ceiling cross-section showing that an alarm must be at least 300 millimetres from the corner of a ceiling and wall and from light fittings, at least 400 millimetres from air conditioner vents and ceiling fan blades, and if on a wall, between 100 and 300 millimetres below the ceiling.CeilingWallno ceiling alarm300mm minWall mount: 100mm to 300mmbelow ceiling, 300mm from a cornerAlarmLight300mm minAir con ventor fan blades:400mm minSloped ceiling: place the alarm 500mm to 1,500mm from the apex.Stairwell: not where an obstruction stops rising smoke reaching it.Not to scale. Distances from Building Fire Safety Regulation 2008 (Qld) s 55C(3).
The placement distances in Queensland's regulation. These are in the law itself, not just guidance.

If the required spot is impracticable, for example an alarm keeps going off from bathroom steam, the Act lets the owner put it at another location that still warns the occupants [Fire Services Act 1990 (Qld)].

When do Queensland smoke alarms have to be replaced?

Section 148A of the Act says the owner must replace an alarm [Fire Services Act 1990 (Qld)]:

  • within 10 years after the day it was manufactured, and
  • immediately, if it doesn't operate when tested.

If the alarm being replaced was hardwired, the replacement must also be hardwired [Fire Services Act 1990 (Qld)]. That rule catches people out. You can't pull down an old 240 volt alarm and stick up a wireless battery one in its place. QFD's fact sheet also says to replace alarms that contain an ionisation sensor, are not interconnected, or are more than 10 years old [QFD fact sheet].

Can I install Queensland smoke alarms myself?

Battery ones, yes. Hardwired ones, no. QFD says hardwired alarms "must be installed by a qualified electrician", while wireless alarms with a non-removable 10-year battery "can be installed yourself" [QFD fact sheet]. The Office of Fair Trading says the same, and adds that homeowners can test their own alarms [QLD Fair Trading]. See DIY or electrician.

What do Queensland landlords and tenants have to do?

The Act splits the duties [Fire Services Act 1990 (Qld)]:

  • Landlord, within 30 days before a tenancy starts: test each alarm, replace any spent or nearly spent battery, and clean each alarm following the maker's instructions. The RTA says this includes the start of a renewed tenancy [RTA].
  • Tenant, during the tenancy: test and clean each alarm at least once every 12 months, replace spent batteries, and tell the landlord as soon as practicable if an alarm has failed or is about to fail for another reason.
  • The landlord cannot make the tenant their agent for the landlord's own duties.

The landlord must give 48 hours' entry notice for smoke alarm work, and a non-working alarm may count as an emergency repair [RTA]. Full detail on landlord obligations and what tenants need to know.

What do Queensland sellers have to do?

On or before the date of possession, the seller must give the buyer written notice of whether compliant smoke alarms are installed [Fire Services Act 1990 (Qld)]. The seller also reports this to the government, which is done through item 5(g) of the Form 24 property transfer form lodged with the titles office [Form 24 guide]. The newer seller disclosure statement (Form 2, from 1 August 2025) does not have a smoke alarm item [Seller disclosure Form 2]. More in selling a house.

What are the penalties in Queensland?

Each smoke alarm offence in the Act carries a maximum penalty of 5 penalty units [Fire Services Act 1990 (Qld)]. A Queensland penalty unit is $172.70 from 1 July 2026 [QLD penalty unit 2026], so by my arithmetic the maximum per offence is $863.50. No official page states that dollar figure, and I did not find any official statement about how the Queensland Fire Department plans to enforce the 2027 deadline. It is also worth knowing that it is an offence to remove an alarm or its battery, or do anything that reduces how well it warns you [Fire Services Act 1990 (Qld)].

Who runs smoke alarm law in Queensland?

The Queensland Fire Department (QFD). It replaced Queensland Fire and Emergency Services (QFES) on 1 July 2024 [QLD media statement], so older articles that mention QFES are talking about the same agency. The RTA says smoke alarm law is administered by QFD under the Fire Services Act 1990 and the Building Fire Safety Regulation 2008 [RTA]. You can call 13 QGOV (13 74 68) for QFD.

Sources

Every source below was read on the official page. Last checked: November 2026.

  1. Queensland Government (qld.gov.au): Smoke alarms (page last updated 29 October 2026)
  2. Queensland Legislation: Fire Services Act 1990, Part 9A, ss 147W to 148K (PDF, current as at 6 December 2025)
  3. Queensland Legislation: Building Fire Safety Regulation 2008, Part 5A, ss 55C to 55E (PDF)
  4. Queensland Fire Department: Smoke alarm laws are changing in Queensland (fact sheet QFE00206, PDF)
  5. Queensland Fire Department: Smoke alarm checklist (QFE00207, PDF)
  6. Queensland Government (qld.gov.au): Renovating and improving (before you put your home on the market)
  7. Office of Fair Trading Queensland: Selling smoke alarms
  8. Residential Tenancies Authority (Qld): Smoke alarms
  9. Titles Queensland: Guide to completing Form 24 Property Information (Transfer) (PDF, March 2025)
  10. Queensland Government: Seller disclosure statement, Form 2, effective 1 August 2025 (PDF)
  11. Queensland Legislation: Penalties and Sentences (Penalty Unit Value) Amendment Regulation 2026
  12. Queensland Government Ministerial Media Statements: New Queensland Fire Department signals dawn of new era for fire services (1 July 2024)